- Model NO.: s-15
- Structure: Three-column Disconnector
- Operation: Manual
- Movement Mode: Horizontal Rotary Type
- Grounding: Single Ground
- Run: Turn the Horizontal
- Structure of Operating: Manual
- Brand: Oei Power
- Specification: IEC62271-102
- HS Code: 8535309000
- Type: High-voltage
- Installation: Outdoor High-voltage
- Grounding Mode: Grounding
- Number of Poles: Three Pole
- Series: Three
- Common Model: Ist
- Certification: IEC IEEE
- Trademark: OEIpower
- Origin: China Nanyang
The Gang operated Air break switches are meant for outdoor application and are suitable for horizontal or
vertical mounting. They are designed for satisfactory performance in harsh atmospheric conditions of
high/low temperatures & humidity. Their primary function is to isolate a 11 kV, 3 Phase network. Asiatic
manufactures the Air break switches in both Porcelain & Silicone rubber versions.
Features
4Single break type with 2 or 3 post insulators per pole depending on requirements of the
customers.
4Can be used for single or three phase applications.
4Robust sturdy design with bottom MS channel of
adequate dimensions which imparts requisite strength.
4Self lubricating central bush bearing in 2 or 3 insulator design of air break switches allows easy
operation.
4Copper contacts are made of ETP grade high conductivity copper and are spring loaded for
adequate contact pressure. The contacts are duly
plated to improve resistance to corrosion and
offers a low resistance current path.
4The Post insulators are available in Porcelain and  Silicone Rubber with large creepage distance
suitable for heavily polluted atmosphere and
meets the stringent requirements of IS/IEC
standards.
4All MS parts and Hardware are duly hot dip galvanized as per standard specifications which
imparts long life to the switch.
4In 3 insulator design, tin plated braided Copper
wire of adequate cross section is provided as per
rating of the GOAB switch and depending upon
customer requirements.
4The Isolator is capable of withstanding the electrical & mechanical stresses induced during unlikely event of short circuits.
4The operation is either hook operated in silicone version through an insulated operating stick or
sturdy operating mechanism is provided allowing easy operation 6 meters above ground level with
simultaneous operation of all the three poles making perfect electrical contact.
4 Mechanical locking facility is provided for closed & open positions as required.
Type test
The GOAB switch in both Porcelain & Silicone Rubber
insulators have been extensively type tested at CPRI - a
laboratory of International repute as per IEC 62271-102 respectively for the following
Tests:
Short Time & Peak withstand Current.
Mechanical Endurance Test.
Lightning Impulse Voltage withstand Test.
High Voltage Dry & Wet Power Frequency Test
Â
Â
 SOLID LINKS 11KV
Â
Â
Â
Â
Â
N/O | DETAIL | DATA | ||
1 | Description | Solid link assembly complete with link rated at 200A and mounting bracket to PIESA 002. (See Figure 1Â to Figure 12 below) |
||
2 | System conditions of service    a) nominal Voltage (Un) r.m.s |
    kV |
    11 |
|
b) maximum system voltage (Um) r.m.s | KV | 12 | ||
c) earthing | Effective & non effective | |||
d) Frequency | Hz | 50 | ||
3 | Site conditions of service a) altitude |
 m |
 1400 |
|
b) Operating Ambient temperature | °C | -1 to 40 | ||
c) Humidity | % | 85 | ||
4 | Rating | |||
a) Nominal voltage | kV | 11 | ||
b) Rated current | Solid link | Â A |
 200 |
|
 Cut out base |
 A |
 200 |
||
5 | Electrical components | |||
a) Insulator material specification | Porcelain | |||
Dielectric strength | ||||
Lightning impulse withstand (1.2/50) | kV | 95 | ||
Power frequency wet withstand voltage r.m.s |
kV | 28 | ||
6 | Specific creepage distance | mm/kV | 25 |
Â
Â
7 | General information to be provided with bid: Drawings and brochures showing outline and general arrangement |
    Yes/No |
    Yes |
b) Detailed drawings of all items showing critical tolerances to be provided with bid |
Yes/No | Yes | |
8 | Previous Type test report/certificate on complete solid link assembly to be provided with bid |
 Yes/No |
 Yes |
10 | Routine tests (acceptance tests on sample Product) to be provided on delivery |
Yes/No | Yes |
11 | Applicable standard | PIESA 002 | |
12 | Other applicable standards | NRS 035 SABS IEC 60282-2 SABS IEC 60186 BS 137 part 2 |
Â
Â
TRI-LINKS
Â
Â
Â
Lot 3-(a) 11kV with interrupters
Â
Â
Â
N/O | DETAIL | DATA | |
1 | TYPE | 11kV pre-assembled gang operated overhead line load break switch complete with expulsion interrupters |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 11 | |
b) maximum voltage (Um) r.m.s | KV | 12 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 400 | |
f) Fault closing capacity | kA | 12.5 | |
4 | Site conditions of service a) altitude |
 metres |
 1400 |
b) Operating Ambient temperature |  °C |
 -1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 95 |
Â
Â
Power frequency wet withstand voltage r.m.s | KV | 28 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: Drawings and brochures showing Outline and general arrangement |
   Yes/No |
   Yes |
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes. |
9 | Routine tests (acceptance tests on sample  Product) to be provided on delivery. |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
Â
Â
FURTHER REQUIREMENTS:
Â
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
Â
Â
Â
SUPPLIMENTARY NOTES
Â
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to customer, It is therefore imperative that schedule "B" is completed by the tenderer. Any deviations/modifications/alternatives specification must be listed in schedule "C.
Â
Â
Â
Â
Â
Â
33kV with interrupters
Â
Â
Â
N/O | DETAIL | DATA | |
1 | TYPE | 33kV pre-assembled gang operated overhead line load break switch complete with expulsion interrupters |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 33 | |
b) maximum voltage (Um) r.m.s | KV | 36 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 200 | |
f) Fault closing capacity | kA | 12.5 | |
4 | Site conditions of service a) altitude |
 metres |
 1400 |
b) Operating Ambient temperature |  °C |
 -1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 170 | |
Power frequency wet withstand voltage r.m.s | KV | 70 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Â
Â
Drawings and brochures showing Outline and general arrangement |
 Yes/No |
 Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample  Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
Â
Â
FURTHER REQUIREMENTS:
Â
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
Â
Â
Â
SUPPLIMENTARY NOTES
Â
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to custoemr.
Â
Â
Â
Â
Â
Â
Â
11kV without interrupters
Â
Â
Â
Â
N/O | DETAIL | DATA | |
1 | TYPE | 11kV pre-assembled gang operated overhead line switch without expulsion interrupters (non-load break switch) |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 11 | |
b) maximum voltage (Um) r.m.s | KV | 12 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 400 | |
4 | Site conditions of service a) altitude |
 metres |
 1400 |
b) Operating Ambient temperature |  °C |
 -1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 95 | |
Power frequency wet withstand voltage r.m.s | KV | 28 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Â
Â
Drawing and brochures showing Outline and general arrangement |
 Yes/No |
 Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample  Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
Â
Â
FURTHER REQUIREMENTS:
Â
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
Â
Â
Â
SUPPLIMENTARY NOTES
Â
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to
Â
Â
Â
Â
Â
Â
33kV without interrupters
Â
Â
N/O | DETAIL | DATA | |
1 | TYPE | 33kV pre-assembled gang operated overhead line switch without expulsion interrupters (non-load break switch) |
|
2 | Mounting configuration | Horizontal | |
3 | Mode of operation | Manually operated pole mounted linking rod and handle with locking facilities |
|
a) nominal Voltage (Un) r.m.s | kV | 33 | |
b) maximum voltage (Um) r.m.s | KV | 36 | |
c) earthing | Effective & non effective | ||
d) Frequency | Hz | 50 | |
e) rated current | Amp | 200 | |
4 | Site conditions of service a) altitude |
 metres |
 1400 |
b) Operating Ambient temperature |  °C |
 -1 to +40 |
|
c) Relative humidity | % | 85 | |
5 | Electrical components | ||
a) Insulator material specification | High Temperature Vulcanised Silicon rubber |
||
b) Cross arm and operating controls materials | Hot dip galvanized steel to SAN760 |
||
Dielectric strength | |||
Lightning impulse withstand (1.2/50) | kV | 170 | |
Power frequency wet withstand voltage r.m.s | KV | 70 | |
Short time current rating -1sec | kA | 12.5 | |
6 | creepage distance | mm/kV | 25 |
7 | General information to be provided with bid: |
Â
Â
Drawing and brochures showing Outline and general arrangement |
 Yes/No |
 Yes |
|
8 | Previous Type test report/certificate on complete assembly to be provided with bid |
Yes/No | Yes |
9 | Routine tests (acceptance tests on sample  Product) to be provided on delivery |
Yes/No | Yes |
10 | Applicable standards | IEC62271 |
Â
Â
FURTHER REQUIREMENTS:
Â
Water shall not be able to accumulate on any part of the equipment nor shall any feature introduce moisture into any component.
The design shall incorporate all reasonable precautions and provisions for the safety of personnel concerned with the operation and maintenance of the same.
The current path shall be such that load current shall only flow through high conductive materials such as copper and its alloys. Load current shall not be permitted to flow through ferrous components, springs, or spring-loaded mechanisms.
All load current paths shall be so designed that the relevant parts of the switch are capable of carrying the specified rated current without exceeding the permitted temperature rise.
Â
Â
Â
SUPPLIMENTARY NOTES
Â
Suppliers should give sufficient information including drawings (which must be brief, clear and to the point) on how their switch designs addresses these requirements. Further, Suppliers may offer better alternatives that are of cost benefits to.